VOC online monitoring equipment operation and maintenance content and responsibilities

2021-09-17

visits:

The following is the VOC online monitoring equipment operation and maintenance content and responsibilities organized by Tangshan Lantian Aoyu Technology Co., Ltd. for you

1. The intended skilled personnel for this service should not be less than 2, and there should be 1 skilled person and 1 full-time inspection channel personnel available for 24 hours × 7 round-the-clock service for this project. And the personnel and auxiliary equipment are reasonable. If there is a special need to replace relevant skilled personnel, please communicate with Party B in a timely manner.

2. In the process of online monitoring, operation and maintenance, if any individual personnel are found to have poor quality or irregular behavior, Party A has the right to propose replacement or dismissal. Party B shall handle it seriously according to Party A's requirements, and if necessary, replace or dismiss them.

3. Responsible for the authenticity, accuracy, reliability, and continuity of data provided by active monitoring equipment.

4. Responsible for the operation management of VOC active monitoring equipment and auxiliary equipment, including network transmission, data collection, equipment protection, maintenance, repair, replacement, and other work that affects the normal operation of the equipment. Responsible for office consumption, personnel compensation, network communication, data transmission, equipment protection, repair, replacement (including replacement equipment during the contract period), transportation, vulnerable consumables and accessories with a unit price of less than 2000 yuan related to operations Other related expenses except for water, electricity, lightning protection, and waterproofing fees required for equipment operation;

5. Protect and inspect online monitoring and maintenance equipment at least once a week, and provide preventive protection from time to time. Strictly follow the HJ/T76-2007 and HJ/T75-2007 standards. Perform zero and span calibration once a week; Conduct monthly comparison and analysis of different methods; Conduct an accuracy check every quarter, with a relative error of no more than ± 5%; The error complies with relevant specifications;

6. Real time monitoring and counter control of active monitoring equipment. It is necessary to conduct data inspection, analysis, and summary of online monitoring and maintenance operations before 10:30 every day, record the monitoring values, fault time period, and adopt corresponding methods for troubleshooting of each equipment; Monthly statistical summary of data; And submit a copy of the inspection protection, repair records, calibration records, comparison tests, records of the number of inspections recognized by the enterprise, and manual data for supplementary testing in case of instrument defects to the enterprise before the 10th day of each month;

7. Once the equipment shows operational defects and requires the replacement of important components, Party A shall make corrections within 48 hours after the purchased parts arrive, and the deadline shall not exceed three days; During the period when the equipment cannot operate normally, manual monitoring should be used to record data, at least 4 times a day; And timely report to Party B.

8. Establish sound rules and regulations, quality control systems, instrument operation procedures, and actively monitor equipment operation records, including personnel training, job responsibilities, equipment defect prevention and emergency measures, as well as inspection, protection, repair records, calibration records, comparative tests, etc., to achieve traceability of instrument operation status and monitoring data;

9. Party A shall conduct quality inspections, comparison and monitoring of individual equipment on a regular or irregular basis; If the inspection and comparison test fail, it is necessary for the operator to make corrections within three days, provided that there is no need to replace important parts.

10. When presenting active monitoring data glue